OPC UA Safety Stack Gets SIL 3 Certification, and UAFX Field-Device Specs Hit Release Candidate

OPC UA Safety Stack Gets SIL 3 Certification, and UAFX Field-Device Specs Hit Release Candidate

OPC UA Safety SIL 3: The Certified Stack and the UAFX Field-Device Release Candidates

A safety protocol specification has never stopped a single machine. What stops machines is certified code running inside safety controllers, light curtains and drives, and until last week OPC UA Safety had a specification and a certified test tool but no independently assessed stack. On 24–25 November 2026, at SPS in Nuremberg, the OPC Foundation announced that TÜV SÜD had certified its OPC UA Safety SIL 3 stack, and that the first OPC UA FX (UAFX) controller-to-device release candidates had gone to member review. Together, those two announcements move safe, vendor-neutral communication from “possible on paper” toward “shippable in a product.” This post explains exactly what was certified and what was not, how the Part 15 protocol detects communication errors, how it compares with PROFIsafe, CIP Safety and FSoE, and what a device maker still has to do.

What this covers: the news, the Part 15 mechanism, error budgets with worked numbers, a protocol comparison, the device certification path, and the UAFX C2D parts.

Context and Background

Functional safety over networks is a solved problem, but it has been solved four or five times. Each major fieldbus family carries its own safety layer: PROFIsafe for PROFIBUS and PROFINET, CIP Safety for EtherNet/IP and DeviceNet, Safety over EtherCAT (FSoE) for EtherCAT. All of them are standardised as Communication Profile Families (CPFs) in IEC 61784-3, the standard that sets the rules for safety communication layers. All of them use the same basic idea, the “black channel”: treat the network as untrusted and detect every relevant fault in the endpoints.

The cost of that fragmentation lands on device makers. A drive vendor selling globally may need two or three safety stacks, each with its own certification file, test tool and conformance programme. Integrators pay for it too, because a mixed-vendor cell often needs safety gateways between ecosystems.

OPC UA Safety, published as OPC 10000-15 (Part 15), is an attempt to give the industry one vendor-neutral safety layer on top of OPC UA. Its history matters for understanding its design. According to the OPC Foundation’s safety page, work began in February 2018 as a joint working group with PROFIBUS & PROFINET International (PI) called “PROFIsafe over OPC UA.” It moved into the Field Level Communications (FLC) Initiative in April 2019, became Part 15 in July 2019, shipped Release 1.04 in October 2019 and Release 1.05 in November 2021. Release 1.04 was evaluated against IEC 61784-3 by TÜV SÜD, and the Foundation’s technical paper states plainly that the protocol is based on PROFIsafe.

Two earlier milestones set up last week’s news. In March 2020 the FLC Initiative funded development of a safety stack, with the German research institute ifak in Magdeburg named as the implementer on its project page. Then, on 10 December 2025, TÜV SÜD certified the OPC UA Safety Compliance Test Tool for client/server communication. A test tool lets you prove conformance; a certified stack lets you skip writing the hardest code yourself.

If you need a refresher on what SIL means and how PFH budgets work, our IEC 61508 functional safety and SIL guide covers the fundamentals this post builds on. For the transport side, see our OPC UA FX field exchange reference architecture.

What exactly was announced

The TÜV SÜD certification press release says the OPC UA Safety Stack achieved functional safety certification for applications up to SIL 3, citing IEC 61508, IEC 61511, IEC 62061 and ISO 13849-1. The Foundation says it will release the certified stack as open-source software. It gives no release date and names no licence, so anyone planning around specific licence terms should wait for the actual repository.

Crucially, the release itself draws the boundary: certification covers the communication stack within its defined scope, not a complete device or application. Manufacturers still have to demonstrate that their products comply.

The second release, on UAFX extending to field devices, reports that Parts 10000-85 (Base Device), 10000-86 (I/O) and 10000-88 (Motion) are ready for member-wide review, alongside updates to Parts 80, 81 and 82. Parts 10000-84 (Profiles) and 10000-87 (Instrumentation) are expected as release candidates within four weeks. More than 30 companies contributed to an FX Demo Wall at SPS 2026, which ran 24–26 November.

How OPC UA Safety SIL 3 Works: The Black-Channel Reference Architecture

OPC UA Safety SIL 3 means a safety layer, defined in OPC 10000-15, that runs only inside two endpoints: a SafetyProvider and a SafetyConsumer. Everything between them, including the OPC UA stack, TSN switches and PubSub or client/server transport, is an untrusted “black channel.” The consumer detects corruption, loss, delay, repetition, insertion and masquerade, and falls back to fail-safe values.

OPC UA Safety SIL 3 black channel architecture with SafetyProvider and SafetyConsumer layers above a standard OPC UA stack

Figure 1: The OPC UA Safety layer sits in the two endpoints only; the OPC UA stack, mapper and network form the untrusted black channel.

Figure 1 shows the split. On each side, a safety application talks to the safety communication layer through a Safety Application Program Interface (SAPI). Below that, an “OPC UA Mapper” moves SPDUs (Safety Protocol Data Units) atomically into and out of ordinary OPC UA variables or methods. The OPC UA stack, the Ethernet or TSN network and every switch in between carry no safety claim at all. Only the SafetyProvider and SafetyConsumer layers must be developed under IEC 61508. The newly certified stack is those two layers, not the device around it.

The black channel is the whole point

The black-channel principle is what makes a vendor-neutral safety protocol economically possible. If the network had to be safe, every switch, router and non-safety OPC UA library would need a certification file. Instead, the safety layer assumes the channel can do anything: flip bits, drop frames, replay old messages, reorder them, delay them, or deliver a message from the wrong sender.

The Foundation’s technical paper maps those failure classes to specific countermeasures, following the IEC 61784-3 approach. Corruption is caught by a data integrity check (a CRC). Repetition, loss, incorrect sequence and insertion are caught by a monitoring number. Unacceptable delay is caught by a timeout. Masquerade and addressing errors are caught by an identifier set combined with the CRC. Timeliness uses the consumer’s local clock, so no synchronised time is needed and no timestamps travel in the message.

This is also why the protocol runs over both client/server and PubSub, with or without TSN. The Foundation lists support for unidirectional, bidirectional and multicast patterns, any topology, and no limit on network components or data rate. Those properties fall out naturally once the network is untrusted by design.

Request and response SPDUs carry the safety evidence

Part 15 uses a request-response pattern even when the underlying transport is publish-subscribe. The SafetyConsumer sends a RequestSPDU carrying three things: a SafetyConsumerID (for diagnostics), a MonitoringNumber (MNR) and a one-octet flags field. The request carries no CRC, because the provider’s answer is what gets checked.

The SafetyProvider answers with a ResponseSPDU. Per clause 7.2 of the Part 15 online reference, it holds SafetyData of 1 to 1,500 octets, always encoded as a structure, followed by a 25-octet safety trailer. The trailer contains the flags, three 32-bit SPDU_ID words, the echoed SafetyConsumerID, the echoed MNR and a 32-bit CRC (1 + 12 + 4 + 4 + 4 = 25 octets). A NonSafetyData field can ride alongside for diagnostics, but it is not CRC-protected and must never feed a safety decision.

Three design choices in that trailer are worth understanding:

  • The MNR starts at 0x100 and changes on every request. Values 0x00–0xFF are reserved. The consumer accepts only the first response matching its current MNR, which kills replays and stale data.
  • The SPDU_ID binds identity into the checksum. It XORs a 128-bit SafetyBaseID, the SafetyProviderID, a SIL-specific constant and a SafetyStructureSignature. A response from the wrong provider, at the wrong SIL, or with the wrong data layout fails the check.
  • The CRC uses polynomial 0xF4ACFB13 over the SafetyData and trailer, with a defined byte order for little-endian and big-endian machines.

The SIL constant is a neat detail. Part 15 defines one 32-bit SafetyProviderLevel_ID per SIL (SIL 3 is 0xDEAA9DEE), chosen for a large Hamming distance. A provider must never include a code for a higher SIL than it supports in its source code, so a lower-SIL device cannot accidentally answer with a higher-SIL identity.

The consumer owns the watchdog and the safe state

The SafetyProvider is close to stateless. The technical paper describes two states, WaitForRequest and PrepareSPDU, and it does not need to know who the consumer is. That makes multicast simple: several consumers each run their own provider–consumer pair against the same data.

The SafetyConsumer does all the judging. It restarts a watchdog, the SafetyConsumerTimeout, before each request. When a valid response arrives in time, the data goes to the safety application with qualifiers marking each value good or bad. When the timeout expires, or a CRC, SPDU_ID, consumer-ID or MNR check fails, the consumer sets SafetyData and NonSafetyData to binary zero and raises FSV_Activated, meaning fail-safe values are active. The application can read that flag and substitute other safe values if zero is not the safe state for a given signal.

Sporadic errors get a narrow tolerance. A configurable SafetyErrorIntervalLimit lets the consumer discard a single bad response and continue, but only if the previous detected error was longer ago than the limit. Two errors inside the window trip fail-safe values. If SafetyOperatorAckNecessary is set, the restart then requires an operator acknowledgement.

What “certified stack” does and does not buy you

A certified stack is a pre-assessed software component for the SafetyProvider and SafetyConsumer boxes in Figure 1. It is not a certified device, a certified safety function or a certified machine. The OPC Foundation’s release says this directly, and it is consistent with how IEC 61508 treats reused software: you inherit evidence, you do not inherit a certificate.

What a device maker gains is large but bounded. They avoid designing, verifying and getting assessed the SPDU state machines, CRC routines and identifier logic, which is the protocol-specific part an assessor scrutinises hardest. What remains is their hardware architecture, diagnostic coverage, the safe integration of the stack on their processor and compiler, the safety manual and the system-level assessment. We return to that path in Figure 4.

Walk-through: SPDU Exchange, Error Budgets and Protocol Comparison

Knowing the fields is one thing. Understanding what happens on the wire, cycle by cycle, and what the numbers mean for a real safety function is what matters when you design a product or a cell. This section walks through the exchange, the consumer’s decision logic, the residual-error budget, and how OPC UA Safety stacks up against the incumbents.

Sequence diagram of OPC UA Safety SIL 3 RequestSPDU and ResponseSPDU exchange with monitoring number and watchdog

Figure 2: One healthy cycle and one timed-out cycle of the Part 15 request–response exchange over the black channel.

One cycle on the wire

Figure 2 traces a normal cycle. The consumer’s safety application calls the SAPI, which restarts the watchdog, increments the MNR and writes a RequestSPDU. The OPC UA Mapper publishes it, either by writing a variable or method argument (client/server) or by placing it in a PubSub dataset. On the provider side, the mapper detects that the RequestSPDU changed, and the provider builds a ResponseSPDU from the latest safety data, the echoed MNR and consumer ID, the SPDU_ID words and the CRC.

The response travels back the same untrusted way. The consumer then runs its checks in a fixed order and either delivers the data or trips to fail-safe values. Retries are the business of the OPC UA stack underneath, not of the safety state machines. The safety layer only cares whether a correct, fresh answer arrived before the watchdog fired.

The second half of Figure 2 shows the failure case. If the response is lost, stuck in a congested switch queue, or arrives with an old MNR, the watchdog expires. The consumer zeros the data, raises FSV_Activated and, depending on configuration, demands operator acknowledgement before resuming.

One mapping subtlety affects your safety manual. In client/server mode, a provider that receives repeated identical requests may answer with either current or initial values, and Part 15 requires the chosen behaviour to be documented in the safety manual. In PubSub mode, the provider’s state machine runs only when the mapper sees a changed RequestSPDU.

Flowchart of OPC UA Safety SafetyConsumer checks for CRC, SPDU ID, monitoring number and timeout leading to fail-safe values

Figure 3: The SafetyConsumer’s acceptance logic. Any failed check counts as a detected error; two inside the SafetyErrorIntervalLimit force fail-safe values.

The consumer’s decision logic

Figure 3 condenses the consumer state machine into its acceptance checks. The order matters less than the rule that every check must pass: CRC match, SPDU_ID match (right provider, right SIL, right structure), consumer-ID match and MNR match. A response that passes all four within the watchdog time is delivered with per-value qualifiers.

A response that fails any check is a “detected error.” What happens next depends on the error-interval timer. If the last detected error was longer ago than SafetyErrorIntervalLimit, the bad response is discarded and the consumer waits for the next one. If not, the consumer activates fail-safe values, and only an operator acknowledgement can clear the latch. A watchdog expiry goes straight to fail-safe values.

This design is a deliberate compromise. Industrial networks do drop occasional frames, and a protocol that tripped on every lost packet would cause nuisance stops. Tolerating isolated errors keeps availability up. Bounding the tolerance with a time window keeps the residual error contribution inside the SIL budget, which is the next topic.

Worked numbers: the residual-error budget

Clause 9 of Part 15 ties the error-interval limit to a maximum SIL and a per-connection residual error contribution. The table below reproduces the spec’s values, as published on the Part 15 system requirements page.

SafetyErrorIntervalLimit Max SIL PFH contribution per logical connection PFDavg (20 years)
6 min SIL 2 < 4.0 × 10⁻⁹ /h < 1.0 × 10⁻⁶
60 min SIL 3 < 4.0 × 10⁻¹⁰ /h < 2.5 × 10⁻⁷
600 min SIL 4 < 4.0 × 10⁻¹¹ /h < 8.0 × 10⁻⁸

The CRC’s conditional residual error probability is stated as at most 4.0 × 10⁻¹⁰. The technical paper adds a caveat: for some specific message lengths, the undetected-error probability of a 32-bit CRC exceeds that value by orders of magnitude, which is why the identifier and MNR checks matter alongside the CRC.

Now put that in context. For a high-demand or continuous-mode safety function, IEC 61508 sets the SIL 3 band at 10⁻⁸ ≤ PFH < 10⁻⁷ per hour. A common engineering convention, rooted in IEC 61784-3 practice, is to let communication consume about 1% of the target. At SIL 3, 1% of 10⁻⁷ is 10⁻⁹ /h. One OPC UA Safety connection at 4.0 × 10⁻¹⁰ /h uses 0.4% of the upper SIL 3 bound.

The number that trips people up is connections per safety function, not connections per plant. Consider an illustrative guard-door function: door switch to safety PLC (one connection), safety PLC to drive Safe Torque Off (a second connection), and a cross-cell stop to a neighbouring controller (a third). Three connections contribute up to 1.2 × 10⁻⁹ /h, which is 1.2% of the 10⁻⁷ ceiling. That is still fine, but it has exceeded the 1% rule of thumb, and it consumes budget your sensor, logic solver and actuator also need. Long chains of controller-to-controller hops in a UAFX architecture deserve the same arithmetic.

These figures are illustrative applications of the spec’s per-connection limits. The real PFH calculation belongs in your verification documents, using the device vendors’ safety manuals.

Worked numbers: watchdog timing (illustrative)

Timing is the other budget. The Foundation’s technical paper shows SafetyConsumerTimeout as, for example, three times the ConsumerCycleTime, and Part 15 requires the consumer cycle to be shorter than the timeout. The spec also notes that in the worst case a safety demand may need to be held for two SafetyConsumerTimeout periods to be seen.

Take an illustrative cell with a 4 ms ConsumerCycleTime and a 12 ms SafetyConsumerTimeout. Worst-case communication contribution to reaction time is on the order of the timeout, plus the provider’s and consumer’s own cycle and processing times. If your safety distance calculation per ISO 13855 assumes a 40 ms total system stopping performance before the mechanical stop, a 12 ms watchdog plus two device cycles leaves limited margin for the drive’s STO reaction. Part 15 requires the safety manual to explain how to compute the safety function response time (SFRT) and who owns ConsumerCycleTime, vendor or integrator. These timings are examples only; use the vendor’s SFRT formula.

The trade-off between availability and response time sits right here. A tight watchdog shortens reaction time but trips on TSN or Wi-Fi jitter. A loose watchdog tolerates jitter but lengthens safety distances. On a deterministic TSN network, as described in our OPC UA over TSN reference architecture, you can set tighter watchdogs with confidence.

PROFIsafe vs CIP Safety vs FSoE vs OPC UA Safety

All four protocols are black-channel designs aimed at SIL 3 under IEC 61508. They differ in ownership, transport binding, connection model and how they establish freshness. The matrix below sticks to well-documented architectural properties; check each organisation’s current specification before using it for a design decision.

Property PROFIsafe CIP Safety FSoE (Safety over EtherCAT) OPC UA Safety (Part 15)
Steward PI (PROFIBUS & PROFINET International) ODVA EtherCAT Technology Group OPC Foundation, with PI
IEC 61784-3 profile CPF 3 (IEC 61784-3-3) CPF 2 (IEC 61784-3-2) CPF 12 (IEC 61784-3-12) Evaluated against IEC 61784-3; not a CPF part as far as I could verify
Typical carriers PROFIBUS, PROFINET EtherNet/IP, DeviceNet EtherCAT, also other black channels OPC UA client/server, PubSub, UAFX, with or without TSN
Role model F-Host and F-Device Originator and target FSoE master and slave Symmetric provider and consumer; any node can be either
Freshness mechanism Consecutive number plus watchdog Time stamps plus time expectation Sequence number plus watchdog Monitoring number plus consumer watchdog
Addressing at runtime Configured F-addresses Configured connections Configured connection IDs IDs can be chosen at runtime, enabling dynamic connections
Max payload per message Small, fixed per configuration Small, configured Small, few bytes per frame 1 to 1,500 octets of structured SafetyData
Maturity Very large installed base Large installed base Large installed base Spec since 2019; first certified stack Nov 2026

Three observations go beyond the table. First, OPC UA Safety inherits PROFIsafe’s freshness model rather than CIP Safety’s time-stamp approach, which is why it needs no clock synchronisation. Second, its symmetric roles fit controller-to-controller exchange better than master–slave models; the incumbents were born in controller-to-I/O topologies. Third, the 1,500-octet structured payload is unusually large. That suits machine-to-machine interlocks and safe motion data, but bigger SPDUs cost CPU time in CRC and checks on small safety MCUs.

None of this makes the incumbents obsolete. A PROFINET plant with thousands of PROFIsafe devices has no reason to migrate. The realistic early use of OPC UA Safety is between controllers from different vendors, where today a hardwired interlock or a safety gateway sits. Our comparison of PROFINET vs EtherCAT vs OPC UA FX over TSN covers the non-safety side of that decision.

UAFX Controller-to-Device Release Candidates: Why They Matter for Safety

The safety stack would be a curiosity without devices to put it in. Until now, UAFX was effectively a controller-to-controller (C2C) technology; the Foundation’s own technical paper says C2D support was coming “soon.” The November release changes that by putting the device information models into member review.

The three parts now in review define what a UAFX field device looks like. Part 10000-85 (Base Device) gives a common information model for all field devices. Part 10000-86 (I/O) covers digital, analog and modular I/O. Part 10000-88 (Motion) covers motion devices such as drives. Maintenance updates and new features for Parts 80, 81 and 82 travel in the same review package. Parts 10000-84 (Profiles, including the new C2D profiles and conformance requirements) and 10000-87 (Instrumentation) are expected as release candidates within about four weeks.

A release candidate is not a published specification. The press release describes member review, then final approval and publication, with no dates. Treat any product claim of “UAFX C2D compliant” before Part 84’s conformance requirements are final with care. For the C2C versus C2D design differences, see our OPC UA FX C2D vs C2C explainer, and for what changed in the current base parts, our breakdown of UAFX v1.00.04 vs v1.00.03 Parts 81–84.

How safety rides inside UAFX

The technical paper says OPC UA Safety is carried inside standard UAFX connections, so the underlying connections need no additional functional safety assessment. That is the black channel working as intended: UAFX connection management, PubSub datasets and TSN streams are just transport. The safety SPDUs travel as data inside them.

This has a practical consequence for device architecture. A UAFX drive with safe motion needs two things: a UAFX communication stack (non-safety, any quality level the vendor chooses) and a safety island running the certified OPC UA Safety stack. The two meet at the OPC UA Mapper. Keeping them on separate cores, or at least separate memory-protected partitions, is the usual way to stop non-safety code from interfering with safety code.

The December 2025 test-tool release also points to what comes next. The certified compliance test tool covers client/server today, and the next phase extends it to PubSub and UAFX. Until PubSub and UAFX test coverage exists, device makers using the safety stack over UAFX will need to agree the conformance evidence directly with their assessor.

The device maker’s certification path

OPC UA Safety SIL 3 device certification path from certified stack integration to assessed safety device

Figure 4: The certified stack is one input; the device still needs its own hardware, integration, conformance testing and assessment.

Figure 4 lays out the path. The certified stack enters as pre-assessed software with its own safety manual and integration constraints, which will define allowed compilers, target assumptions and required checks. ifak’s original project description targeted MISRA-C:2012 and portability across processors, byte orders and compilers, though the final certificate’s conditions are what count.

From there, the device maker integrates the stack into a safety architecture that reaches SIL 3. ifak’s project page described the stack as suitable for single-channel designs up to SIL 2 and two-channel designs up to SIL 3; whether the certified release keeps that split depends on the certificate. Either way, the hardware fault tolerance, diagnostic coverage and safe failure fraction come from the device design under IEC 61508-2, not from the stack.

Next comes the device-specific work Part 15 mandates. Clause 9 requires persistent storage of SafetyBaseID and SafetyProviderID, protection against MNR values collapsing to a small set (save MNR on shutdown or seed it randomly on restart), a visible indication when operator acknowledgement is requested, and a safety manual that states PFH per logical connection and explains SFRT calculation. Then the device passes conformance testing with the OPC UA Safety test tool, and a notified body assesses the whole product.

The certified stack shortens the longest pole, the protocol software assessment. It does not remove the device assessment, and it cannot.

Trade-offs, Gotchas, and What Goes Wrong

“Certified stack” will be misread as “certified device.” Expect marketing slides that blur the two. A device is only SIL 3 when its own assessment says so. The OPC Foundation’s release is explicit on this, and procurement teams should ask for the device certificate, not the stack certificate.

Open source does not mean free of obligations. The Foundation says the stack will be released as open source, but no licence or date has been published. A safety certificate typically applies to a specific, unmodified release built under stated conditions. If you patch the code, you likely step outside the certificate’s scope and must re-justify the change. Plan for the stack to be a vendored, frozen dependency rather than a fork you maintain.

The error-interval window is a hidden availability knob. At SIL 3, the spec ties the error-interval limit to 60 minutes. Two detected errors within an hour on one connection trip fail-safe values and may need an operator acknowledgement. On a noisy wireless link or a congested converged network, that can mean nuisance stops. Part 15 says frequent acknowledgements, more than once a day at SIL 2 or SIL 3, indicate a problem with installation, interference, traffic load or transmission quality. Treat them as a network health alarm, not as normal operation.

Zero is not always safe. The default fail-safe value is binary zero. For a “stop” bit that is fine; for an analog setpoint, a valve position or a safe speed limit, zero may be the wrong state. The application must read FSV_Activated and apply signal-specific safe values.

NonSafetyData is a trap. It travels in the same ResponseSPDU and looks convenient, but it is not CRC-protected. Using it in any safety decision voids the argument.

Large payloads cost cycles. The 1,500-octet ceiling is generous, but CRC calculation over large SafetyData on a small dual-core safety MCU eats into the cycle budget. Keep SafetyData to what the safety function needs; move diagnostics to ordinary OPC UA variables.

Configuration identity errors are common. SafetyBaseID, SafetyProviderID and SafetyStructureSignature must match on both ends, and zero values are invalid. A device swap that loses persistent IDs, or a structure change on one side only, will fail SPDU_ID checks. That is safe, but it is a commissioning headache if your tools don’t make the identifiers visible.

Release candidates move. UAFX C2D parts in member review can still change. Building silicon or firmware against a release candidate is a reasonable bet for prototypes, not for frozen designs.

Security is a separate layer. OPC UA Safety detects masquerade by accidental or random faults within its error model; it is not a defence against a deliberate attacker who can compute CRCs. You still need OPC UA security policies, certificate management and network segmentation per IEC 62443.

Practical Recommendations

For device makers, the certified stack is the strongest reason yet to put OPC UA Safety on the roadmap, especially for products that must talk safely to controllers from more than one vendor. Start now with the Part 15 specification and the compliance test tool. Architect a clean safety island with a narrow mapper interface. Budget for the device-level assessment, because the stack certificate does not replace it. Wait for the published repository and its certificate conditions before fixing compilers, MCU targets or licence assumptions.

For machine builders and integrators, the realistic first wins are vendor-neutral controller-to-controller safety interlocks that currently need hardwiring or a gateway. Count logical connections per safety function and add their PFH contributions explicitly. Size watchdogs against measured network jitter, not datasheet nominal cycle times.

For end users and plant owners, ask suppliers three questions: is the device itself assessed for OPC UA Safety at the SIL you need, which Part 15 release does it implement, and which transport mappings (client/server, PubSub, UAFX) are covered by conformance testing.

A short checklist:

  • Separate “stack certified” from “device certified” in every requirement and purchase spec.
  • Record SafetyBaseID, SafetyProviderID and SafetyStructureSignature in commissioning documents.
  • Set SafetyErrorIntervalLimit to the value your SIL requires, and alarm on acknowledgement frequency.
  • Define signal-specific fail-safe values wherever zero is not the safe state.
  • Keep NonSafetyData out of safety logic.
  • Treat UAFX C2D parts as release candidates until published, and track Part 84 conformance.
  • Layer OPC UA security and IEC 62443 controls on top of, not instead of, the safety layer.

If you are still choosing between information-model approaches for the non-safety side, our complete OPC UA protocol guide is a useful companion.

Frequently Asked Questions

What does OPC UA Safety SIL 3 certification actually cover?

It covers the OPC Foundation’s OPC UA Safety communication stack, the software that implements the Part 15 SafetyProvider and SafetyConsumer layers. TÜV SÜD certified it for use in applications up to SIL 3, citing IEC 61508, IEC 61511, IEC 62061 and ISO 13849-1. It does not certify any device, safety function or machine. A manufacturer that uses the stack still needs its own hardware design, integration, conformance testing and independent assessment before claiming a SIL for a product.

Is the OPC UA Safety stack open source, and under what licence?

The OPC Foundation says it will make the certified stack available as open-source software. As of 29 November 2026, its announcement gave no release date and named no licence. Until the repository appears, do not assume specific licence terms, contribution rules or certificate conditions. Remember that safety certificates usually apply to a defined, unmodified release built under stated constraints, so changing the code may take you outside the certified scope.

What is the black channel principle in OPC UA Safety?

The black channel principle treats everything between two safety endpoints as untrusted. That includes the OPC UA stack, switches, routers and TSN infrastructure. The safety layer in the SafetyProvider and SafetyConsumer detects corruption with a CRC, repetition and loss with a monitoring number, delay with a watchdog, and masquerade or addressing errors with an identifier set. Because the channel carries no safety claim, standard non-safety networking equipment can carry safety data.

How is OPC UA Safety different from PROFIsafe?

OPC UA Safety grew out of a 2018 “PROFIsafe over OPC UA” working group, and the Foundation’s technical paper says it is based on PROFIsafe. The main differences are symmetric roles, where any node can be provider or consumer, identifiers that can be set at runtime for dynamic connections, structured payloads up to 1,500 octets, and transport over OPC UA client/server, PubSub or UAFX instead of PROFINET. PROFIsafe has a far larger installed base today.

Can OPC UA Safety run over PubSub and TSN?

Yes. Part 15 defines mappings for both OPC UA client/server and PubSub, and the Foundation states it works with or without TSN. In PubSub, the provider’s state machine runs when the mapper sees a changed RequestSPDU. Note that the TÜV SÜD-certified compliance test tool covered client/server as of December 2025, with PubSub and UAFX support announced as the next phase. Check current conformance coverage before relying on PubSub in a certified product.

When will the UAFX controller-to-device specifications be final?

The OPC Foundation has not published a final date. Parts 10000-85, -86 and -88 entered member-wide review as release candidates in November 2026, and Parts 10000-84 and -87 were expected as release candidates within about four weeks. Final approval and publication follow member review. Until then, treat the content as subject to change and avoid freezing product designs to release-candidate text.

Further Reading